Skip to content

Steep-Slope Systems

30% of this exam

Shingle, tile, and metal systems: where each is allowed by slope, how each is attached, and the flashing details that keep water out at every edge, wall, and penetration. The exam tests the details — nailing zones, starter strips, valley types, and the two-part flashing logic — more than the field shingling itself.

What the exam asks

  • Which covering is allowed at which slope, and how many underlayment layers each slope needs.
  • Shingle fastening: the nail zone, nail count, nail size and what high nailing does.
  • Flashing logic: step flashing under counterflashing, kickouts, valleys and the 30-inch cricket rule.
  • Tile weight and attachment, and the metal panel types and their minimum slopes.

Part 1 of 4

Slope and underlayment

Slope decides which covering you can use, and slope also decides how much underlayment goes under it. Get these two straight and a lot of the questions answer themselves.

Slope decides the system

Asphalt shingles want 4:12 and steeper but are permitted down to 2:12 with enhanced underlayment per code and manufacturer. Below 2:12 is membrane territory — no shingles. A roofing square is 100 square feet, the unit everything is sold and estimated in.

Work it: Squares, waste and bundles

Squares = Roof area ÷ 100. Order squares = Squares × (1 + Waste). Bundles = Order squares × Bundles per square.

ft
ft
%

Roof area

2 × 60 ft × 28 ft equals 3,360 SF

Squares of roof

Roof area ÷ 100 equals 33.6

Squares to order with waste

Squares × (1 + 10%) equals 37.0

Bundles to order

Squares to order × 3 equals 111

Underlayment is the roof under the roof

Asphalt shingles need one layer of underlayment at 4:12 and steeper and two layers (lapped 19 inches) between 2:12 and 4:12. Tile and metal carry their own underlayment schedules, usually a two-ply or self-adhered cap-sheet system in Florida. The Florida Building Code's sealed-roof-deck provisions add a self-adhering membrane over the deck joints or over the whole deck so the house stays dry when the covering blows off — in the HVHZ the underlayment itself is a product-approved system.

Worked examples

Fig — Asphalt shingle slope limits
  1. Absolute minimum slope2 in 12

    Only with the enhanced underlayment the code and manufacturer require.

  2. Standard minimum slope4 in 12

    Where shingles perform best; normal underlayment rules apply.

Fig — Minimum slopes for steep-slope coverings
  1. Standing-seam metal0.25 in per ft
  2. Lapped metal with sealant0.5 in per ft
  3. Asphalt shingles (two underlayment layers)2 in per ft
  4. Clay / concrete tile2.5 in per ft
  5. Lapped metal, no sealant3 in per ft
  6. Asphalt shingles (one layer)4 in per ft

In your books: Slope minimums and underlayment layers are FBC Chapter 15 numbers, section 1507 by covering type. Tab each covering's section. For the systems themselves, tab each one separately in the NRCA manual's steep-slope sections.

Part 2 of 4

Fastening and edge details on shingles

Shingle roofs fail at the nail. This part covers where nails go, how many, and the edge pieces that finish the roof.

Fastening is where shingle roofs fail

Nails go in the manufacturer's designated nailing zone — generally just below the sealant strip — so each nail catches the top of the course below. High nailing misses that course and is a leading cause of blow-offs. Tile attaches mechanically (screws/nails) or with foam adhesive, always per the product approval.

Nails: count, length, placement

Shingles get a minimum of four nails, six in high-wind areas (which in Florida means six), 12-gauge with 3/8-inch heads, driven flush — not overdriven — through the nail zone below the sealant strip so each nail also catches the course below. Nails penetrate 3/4 inch into the deck or through it. Drip edge laps 2 inches and is fastened 12 inches on center; starter strips go at eaves and rakes with the sealant at the edge. Blow-offs trace back to high nails, short nails and missed nail zones.

Edges and accessories finish the system

Drip edge directs runoff clear of the fascia at eaves and rakes; starter strips seal and back up the first course's joints; hips and ridges get lapped cap shingles installed last. Ridge vents only work with roughly balanced soffit intake.

In your books: Nail count and the other fastening numbers are FBC Chapter 15 lookups. Check the book rather than answering from memory.

Part 3 of 4

Flashing, valleys and penetrations

Water gets in where the roof meets something else. Flashing works in layers, each piece lapped over the one below it, so the order matters as much as the part.

Flashing is a layered, lapped system

Step flashing weaves one piece into each course at sidewalls; a kick-out at the bottom throws water into the gutter instead of behind the siding. Counterflashing attaches to the wall and laps over the base flashing. Crickets divert water around the high side of chimneys wider than 30 inches.

Valleys, walls and penetrations

An open valley is lined with metal at least 24 inches wide over a 36-inch strip of underlayment; closed-cut and woven valleys use the shingles themselves. Step flashing at sidewalls is at least 4 by 4 inches, one piece per course, under a counterflashing; a kickout at the bottom of a sidewall sends water into the gutter instead of behind the siding. Chimneys wider than 30 inches need a cricket on the up-slope side. Pipe boots, ridge vents and skylight curbs are the other usual leak sites.

In your books: The 30-inch cricket rule is a code lookup. Check the FBC roofing chapter rather than answering from memory.

Part 4 of 4

Tile and metal systems

Tile and metal each have their own weight, slope, attachment and corrosion rules. The exam tests the differences between the types.

Tile is a dead load and a wind load

Concrete and clay tile weigh roughly 9 to 12 lb per sq ft, so the structure is checked before a shingle roof is re-covered in tile. Attachment is by screws or nails through the tile, foam adhesive, or mortar set — each with its own product approval and the Florida tile manual's (FRSA/TRI) details for hips, ridges, eave closures and bird stops. Minimum slope is 2½:12 with double underlayment below 4:12, and battens or batten-and-counterbatten systems let the roof drain under the tile.

Metal: clips move, screws don't

Standing-seam panels hang on concealed clips that let the panel expand and contract; mechanically seamed standing seam can go as low as 1/4:12. Exposed-fastener (through-fastened) panels use gasketed screws, need 3:12 (or 1/2:12 with lapped sealant), and are tested where the screw holes elongate with thermal movement. Keep dissimilar metals apart — copper over aluminum or galvanized steel runoff corrodes the lower metal — and use the SMACNA Architectural Sheet Metal Manual for flat-seam, soldered and gutter work.

In your books: System questions route to the NRCA manual's steep-slope sections, so tab tile and metal separately. The Florida tile manual (FRSA/TRI) has the hip, ridge, eave closure and bird stop details, and the SMACNA Architectural Sheet Metal Manual covers flat-seam, soldered and gutter work.

Know these cold

The short list to have in your head on exam day. Every line is also a card in your flashcards.

Shingle slope limits
4:12 standard; 2:12 minimum with enhanced underlayment; below 2:12 use a membrane
Nail placement
Manufacturer's nailing zone, below the sealant strip — high nailing causes blow-offs
Chimney cricket trigger
Required when the chimney is wider than 30 inches
Tile attachment
Mechanical (screws/nails) or foam-set adhesive, per product approval
Metal panel types
Standing seam = concealed clips; exposed-fastener = gasketed screws through the face
Underlayment types
Felt and synthetic are nailed; self-adhered bonds to the deck and seals around fasteners
Underlayment by slope (shingles)
2:12 to 4:12 → two layers (19-in laps); 4:12 and up → one layer. Below 2:12 shingles are not allowed.
Nail count
4 per shingle minimum; 6 in high-wind regions — Florida. 12-gauge, 3/8-in head, driven flush.
Nail penetration
3/4 in into the deck, or through it when the deck is thinner.
Drip edge
2-in laps, fastened 12 in on center; under the underlayment at the eave, over it at the rake.
Open valley metal
At least 24 in wide, over a 36-in underlayment strip.
Step flashing
Minimum 4 in × 4 in, one piece per course, under a counterflashing with a kickout at the bottom.
Tile dead load
About 9–12 lb per sq ft — check the structure before converting a shingle roof.
Tile minimum slope
2½:12, with double underlayment below 4:12.
Metal panel minimum slopes
Standing seam ¼:12 · lapped with sealant ½:12 · lapped without sealant 3:12.
Galvanic pairs
Copper runoff onto aluminum or galvanized steel corrodes it; separate dissimilar metals or isolate them.

Where it lives in your books

The real exam is open book. Knowing which book and which tab answer this topic is worth as much as memorizing it.

Reading isn't learning. Retrieval is.

98 questions in this domain, each with an explanation and source.