Skip to content

Controls & Electrical

15% of this exam

The 24-volt control world and the motors it commands: how the transformer feeds the thermostat, what each terminal letter does, classic capacitor failure symptoms, and just enough Ohm's law to check a circuit. Smallest domain, fastest points — every fact here is memorizable. The exam's testing area adds field measurements: clamp-on ammeter technique, three-phase power (× 1.732 × PF), kWh cost arithmetic, voltage drop across a loaded contact, testing starters and defrost thermostats, and reversing a three-phase motor by swapping two leads.

What the exam asks

  • Terminal letters on the thermostat and what each one energizes on a cooling call.
  • The classic symptom pattern: a motor that hums but will not start points to the run capacitor.
  • Straight plug-in math: Ohm's law, watts and amps, kWh cost, transformer VA, three-phase power and voltage imbalance.
  • Field measurements: clamp-on ammeter technique, voltage drop across a closed contact, and ohmmeter readings on a compressor.
  • Control sequences: the gas furnace order of operation and safeties wired in series.

Part 1 of 5

The 24-volt control circuit

Everything starts with a small transformer and a thermostat that routes its 24 volts. Know the terminal letters and what happens on a cooling call and these become free points.

The transformer makes the control circuit

A small transformer steps line voltage down to 24 volts AC for the control circuit. The thermostat is just a switch panel routing that 24V to loads: the compressor contactor coil, the blower relay, the reversing valve solenoid. Low voltage means lighter wire and safer service.

Know the terminal letters

R is the 24V hot feed, C the common return to the transformer, Y the compressor contactor (cooling call), G the indoor blower relay, W the heat call. A cooling call closes R-to-Y and R-to-G. Terminal-matching questions are free points.

A cooling call, step by step

The thermostat sends 24 volts out Y to pull in the outdoor contactor, which powers the compressor and condenser fan together, and out G to the indoor blower relay. A contactor and a relay work the same way; the contactor is the heavy-duty one built for compressor current. A single-pole contactor opens only one leg of a 240-volt unit, so the other leg stays live with the unit off. Pull the disconnect before you reach in.

What the thermostat is really doing

A thermostat controls to the temperature it feels, so one mounted in the path of a supply register short-cycles the system. A heat anticipator ends the heating call slightly early so the room coasts to setpoint. Staging brings on the second stage only when the first cannot hold. The C wire gives the thermostat continuous power. Jumpering R to Y at the thermostat is the quick test: if the condenser runs, the thermostat is the problem.

In your books: These are memory questions. The books will not rescue you in time, so drill the terminal letters until they are reflexes.

Part 2 of 5

Sequences and safeties

Furnaces light in a fixed order, and the safety switches sit in the control path to stop the equipment when something is wrong. Heat pumps add a reversing valve and a defrost permission switch.

A gas furnace lights in a fixed order

The induced-draft motor starts first and has to close the pressure switch to prove the vent. Only then does the igniter heat and the gas valve open. The flame sensor must confirm ignition or the board shuts the gas off. The blower waits a short on-delay so it does not push cold air, and runs a short off-delay at the end to deliver the heat still in the exchanger.

Safeties are wired in series

Safety switches sit in series in the 24-volt path to the contactor coil, so any one opening stops the compressor. The low-pressure switch opens on low suction: low charge, a starved metering device, or no airflow. The high-pressure switch is a manual-reset safety so someone finds the cause before it restarts. A condensate float switch breaks the cooling call. An anti-short-cycle delay holds the compressor off a few minutes so pressures can equalize.

Work it: Low-pressure control cut-in

Cut-in = Cut-out + Differential

psig
psig

Cut-in pressure

20 psig + 15 psig equals 35 psig

Heat pump terminals and defrost

O/B drives the reversing valve: most brands energize it in cooling (O), some in heating (B). A heat pump that heats on a cooling call and cools on a heating call is working fine with the O/B setting backward. The defrost thermostat is a normally open switch that closes at roughly 30°F coil temperature and opens at 50 to 70°F. It only gives permission; the board starts the defrost.

Worked example

Fig — Gas furnace sequence of operation
  1. Step 1Thermostat calls for heat (R to W)
  2. Step 2Induced-draft motor starts

    It must close the pressure switch to prove the vent

  3. Step 3Igniter heats, then the gas valve opens

    Never gas first

  4. Step 4Flame sensor confirms ignition

    No flame signal and the board shuts the gas off

  5. Step 5Blower starts after a short on-delay

    So it does not push cold air

Part 3 of 5

Motors and capacitors

A motor that hums but will not start is the classic capacitor symptom. Learn that pattern, the three kinds of capacitor, and how PSC, ECM and three-phase motors differ.

Hums but won't start = capacitor

A PSC motor needs its run capacitor to develop starting torque. With a failed capacitor the motor hums and stalls, but runs if you spin the shaft — torque is only missing at startup. That symptom pattern means capacitor, not contactor, thermostat, or charge.

Start, run and dual capacitors

A run capacitor stays in the circuit the whole time. A start capacitor is in for seconds only, and a potential relay drops it out at about three-quarters speed. A dual run capacitor has three terminals: C, HERM for the compressor and FAN for the condenser fan. Replace a capacitor with the same microfarads and an equal or higher voltage rating. Discharge it through a resistor before touching it, not with a screwdriver.

PSC, ECM and three-phase motors

An ECM is a brushless DC motor that varies its speed; set for constant airflow it holds CFM as the filter loads and its wattage climbs. A PSC motor just moves less air. Locked rotor amps are the inrush at start, several times the rated load amps. Three-phase motors need no capacitor. Even a small voltage imbalance between phases causes a much larger current imbalance and overheats the windings.

Work it: Three-phase voltage imbalance

Imbalance = Largest deviation from the average ÷ Average × 100

V
V
V
V

Average voltage

(234 V + 240 V + 246 V) ÷ 3 equals 240 V

Voltage imbalance (do not use the full spread between high and low)

6 V ÷ average × 100 equals 2.5%

In your books: If a troubleshooting question confirms the motor has power (it hums), eliminate every upstream answer, the thermostat and the contactor, before reading further.

Part 4 of 5

Electrical math and the nameplate

Expect one straight calculation. Write the formula first and the distractors fall away. The nameplate numbers tell you what wire and protection the unit needs.

Ohm's law settles current questions

I = E ÷ R. A 12-ohm contactor coil across 24V draws 2 amps. Expect one straight plug-in calculation; write the formula first and the distractors fall away.

Work it: Ohm's law

Current = Voltage ÷ Resistance

V
ohms

Current drawn

24 V ÷ 12 ohms equals 2.0 A

Power, energy and transformer math

P = E × I. A 4,800-watt heater on 240 volts draws 20 amps, which sizes the wire and breaker. Kilowatts are a rate and kilowatt-hours are a quantity: 5 kW for 8 hours is 40 kWh, or $4.80 at 12 cents. A control transformer is rated in volt-amps: a 24-volt circuit drawing 2 amps needs at least 48 VA. The usual residential transformer is 40 VA.

Work it: Watts to amps

Power = Volts × Amps, so Amps = Watts ÷ Volts

W
V

Current, which sizes the wire and breaker

4,800 W ÷ 240 V equals 20 A

Work it: Energy and what it costs

kWh = kW × Hours. Cost = kWh × Rate

kW
hours
cents

Energy used

5 kW × 8 hours equals 40 kWh

Cost

kWh × 12 cents cents equals $4.80

Work it: Transformer VA

VA = Volts × Amps

V
A

Minimum transformer rating

24 V × 2 A equals 48 VA

Work it: Three-phase power

Watts = Volts × Amps × 1.732 × Power factor

V
A
%

Real power

240 V × 20 A × 1.732 × power factor equals 7,067 W

Nameplate numbers: MCA and MOCP

MCA is the minimum conductor ampacity; MOCP is the largest fuse or HACR breaker allowed. The disconnect must be within sight and readily accessible, and a service receptacle within 25 ft on the same level.

Work it: Minimum circuit ampacity

MCA = 125% of the largest motor load + the other loads

A
A

Minimum circuit ampacity. Wire to this number; the breaker can be anything up to the MOCP.

1.25 × 20 A + 3 A equals 28 A

Part 5 of 5

Measuring and testing

Field tests only help if you take them right. Know how to clamp, what a voltage drop means, and how to read a compressor with an ohmmeter.

Measure it right before you judge it

Clamp one conductor, not the cord. A closed contact should read near zero volts under load; several volts means it is burning. A magnetic starter that will not reset has a tripped overload for a reason. A defrost thermostat is tested in ice water for continuity.

Testing a compressor with an ohmmeter

Kill the power, prove it dead and isolate the component before using an ohmmeter. On a single-phase compressor the highest reading is run to start, because it measures both windings in series; the terminal left over is common. Common to run is the lowest reading. If every reading through common is open but run to start is normal, the internal overload is open: let the shell cool and retest. A megohmmeter checks winding insulation to ground.

Worked example

Fig — Finding common, start and run
  1. Readings
    A to B = 7 Ω, C to A = 2 Ω, C to B = 5 Ω
  2. Highest pair is run to start
    A to B = 7 Ω, so C is common
  3. Lowest from common is run
    C to A = 2 Ω, so A is run and B is start
  4. Check
    2 + 5 = 7 Ω

    The two windings in series add up to the run-to-start reading.

Know these cold

The short list to have in your head on exam day. Every line is also a card in your flashcards.

Control circuit voltage
24V AC, stepped down from line voltage by the control transformer
Thermostat terminals
R = 24V power, C = common, Y = compressor (cool), G = blower fan, W = heat
PSC motor hums, runs when spun
Failed run capacitor — no starting torque
Ohm's law
I = E ÷ R (24V across 12 Ω = 2 A)
Three-phase power
W = V × I × 1.732 × PF.
Reverse a three-phase motor
Interchange any two supply leads. (A scroll compressor that runs backward is loud and does not pump.)
Pneumatic control pressures
Main air about 15–20 psig; actuators stroke over 3–15 psig; at setpoint a proportional thermostat should sit near mid-range (8–9 psig).
Gas manifold pressure
About 3.5 in. w.c. natural gas; about 10–11 in. w.c. propane.
Contactor vs relay
Same principle; a contactor is rated for compressor and large motor current, a relay for light loads.
Single-pole contactor
Breaks one leg only. The other 240 V leg stays live at the compressor with the unit off.
O/B terminal
Reversing valve. O = energized in cooling (most brands); B = energized in heating.
Defrost thermostat
Normally open; closes at roughly 30°F coil temperature, opens at 50 to 70°F. Test it in ice water with an ohmmeter.
Potential relay
Senses back-EMF and drops the start capacitor at about 3/4 of full speed.
Dual run capacitor terminals
C = common, HERM = compressor, FAN = condenser fan motor.
Capacitor replacement
Same microfarad rating; voltage rating equal to or higher than the original.
LRA vs RLA
Locked rotor amps = starting inrush, several times the rated load (running) amps.
Compressor terminals by resistance
Run to start is highest and equals the other two added together; common to run is lowest; common to start is in between.
Voltage imbalance
Largest deviation from the average ÷ average × 100 (234, 240, 246 V = 2.5%).
Power formula
P = E × I (240 V × 15 A = 3,600 W); I = P ÷ E (4,800 W ÷ 240 V = 20 A).
Energy cost
kWh = kW × hours; cost = kWh × rate (5 kW × 8 h = 40 kWh).
Transformer sizing
VA = volts × amps (24 V × 2 A = 48 VA minimum). Typical residential transformer: 40 VA.
Low-pressure control
Cut-in = cut-out + differential (20 + 15 = 35 psig).
High-pressure switch
A safety, usually manual reset. Causes: failed condenser fan, dirty coil, overcharge, non-condensables.
Control wiring
24 VAC, NEC Class 2: 18 AWG thermostat cable, no conduit, kept clear of line-voltage wiring.
MCA calculation
125% of the largest motor load plus the other loads. Wire to the MCA; the breaker may be anything up to the MOCP.
Disconnect and service receptacle
Disconnect within sight of the unit and readily accessible (NEC 440.14); a 125 V receptacle within 25 ft on the same level.
Belt-drive blower speed
Opening a variable-pitch motor sheave slows the blower; closing it speeds it up. Tension: about 1/64 in. deflection per inch of span.
Oil burner
Nozzles are rated in gallons per hour at 100 psi; the cad cell proves the flame or the primary control locks out.

Where it lives in your books

The real exam is open book. Knowing which book and which tab answer this topic is worth as much as memorizing it.

Reading isn't learning. Retrieval is.

80 questions in this domain, each with an explanation and source.