NFPA 14 — Standard for the Installation of Standpipe and Hose Systems
Standpipe classes, system types, hose connections, fire department connections, pressures, and acceptance testing. Fire protection is 5% of the plumbing trade exam and NFPA 14 is its only approved book.
15 questions in our bank cite this reference.
Short answer
NFPA 14 is on the Florida Plumbing Trade Knowledge approved reference list in the 2019 edition. Our tab set marks 7 spots in book order, from Definitions — classes and system types (Ch. 3) to Acceptance testing (Ch. 11). 15 of our practice questions cite it.
On the state's approved list
The list entry this guide covers, in the printing the answer key follows. Check the cover before you tab.
- NFPA 14 — Standard for the Installation of Standpipe and Hose Systems2019
NFPA
Editions match the DBPR reference lists (valid January 2026 – December 2026). Last checked September 25, 2026. Every question is reviewed by a Florida-licensed contractor who holds Certified Building and Class A HVAC licenses and has passed the state General Contractor exams.
The one thing to know
Almost every NFPA 14 question is a classification question: which class (I, II, III), which system type (wet, dry, manual, automatic, semiautomatic), or which pressure limit. Tab the definitions and the pressure table and the rest is reading.
Your tab set
Florida exams allow pre-tabbed, highlighted references. Place these tabs before exam day, in book order, and tick them off here.
0 of 7 tabs placed
- 1Definitions — classes and system typesCh. 3
Class I (2-1/2 in., fire dept), Class II (1-1/2 in., trained occupants), Class III (both); wet/dry/manual/automatic/semiautomatic
- 2System components and hardwareCh. 4
Hose connections, valves, gauges, signs, cabinets
- 3Water supplyCh. 5–6
Required supply, fire pumps, FDC supplying manual systems, piping between FDC and system
- 4Hose connection locations7.3
Exit stair enclosures, horizontal exits, roof, travel distance to connections
- 5Design pressures and flow7.8 / 7.10
Minimum residual pressure 100 psi (Class I/III) and 65 psi (Class II); maximum 175 psi at hose connections; pressure-regulating devices; flow rates
- 6Fire department connections7.12
Location, number, height, signage, check valve and no shutoff between FDC and system
- 7Acceptance testingCh. 11
Hydrostatic test at 200 psi or 50 psi above max for 2 hours, flow tests, flushing, main drain test
Highlight the question, underline the answer
Don't just tab your books — mark them as you practice. Every time a question sends you into a reference, leave a two-part mark behind: highlight the passage the question is about, and underline the exact words that answer it. Do this through your whole question bank and the book turns into a map of the tested material — so on exam day you recognize the spot, not just the section.
- 1
Highlight what the question asks about
When you look up a practice question, highlight the sentence or table the question turns on. That block is now a visual landmark you'll spot on a fast flip.
- 2
Underline the exact answer
Inside the highlight, underline the specific number, deadline, or phrase that is the answer — with a fine-tip pen. Highlight = the topic; underline = the fact.
- 3
Color-code by what trips you up
Use one highlighter color for deadlines and numbers, another for definitions, a third for the answers you got wrong twice. Your weak spots become the brightest marks in the book.
- 4
Let your tabs and marks compound
A tab gets you to the chapter; the highlight gets you to the paragraph; the underline gets you to the answer. Built up across a full question bank, that three-layer trail is the open-book skill the exam actually tests.
The reference lists allow underlining with pen or highlighter, bar handwritten and typewritten notes in the books, and bar making any marks during the exam — so every mark goes in before you walk in, and none of them can be written notes.
Navigating under time pressure
- Classes (I, II, III) and system types (automatic-wet, automatic-dry, semiautomatic-dry, manual-wet, manual-dry) are both in Chapter 3 definitions — most questions are answered there.
- Design pressures, hose connection locations, and FDC rules are in Chapter 7; acceptance tests (hydrostatic, flow) are in Chapter 11.
- NFPA 14 is standpipes only — sprinkler questions are NFPA 13 material and are not on the plumbing list.
Frequently asked questions
Which edition of NFPA 14 does the Florida exam use?
The 2019 edition, per the DBPR list for the Plumbing Trade Knowledge exam. The answer key follows that printing.
How should I tab NFPA 14 (Standpipes) for the exam?
Almost every NFPA 14 question is a classification question: which class (I, II, III), which system type (wet, dry, manual, automatic, semiautomatic), or which pressure limit. Tab the definitions and the pressure table and the rest is reading. Build the 7-tab set on this page before exam day, in book order, with permanent tabs that carry only the section heading; movable flags and written notes are not allowed in the exam room.
How do I find answers in NFPA 14 (Standpipes) quickly?
Classes (I, II, III) and system types (automatic-wet, automatic-dry, semiautomatic-dry, manual-wet, manual-dry) are both in Chapter 3 definitions — most questions are answered there. Design pressures, hose connection locations, and FDC rules are in Chapter 7; acceptance tests (hydrostatic, flow) are in Chapter 11. NFPA 14 is standpipes only — sprinkler questions are NFPA 13 material and are not on the plumbing list.