Ductwork & Ventilation
20% of this examMoving the right amount of air and keeping it in the duct: sizing with the Ductulator, SMACNA fabrication rules (pressure class, seal class, seams, joints, reinforcement), fibrous glass and flexible duct limits, NFPA 90A/90B installation rules, NFPA 96 grease hoods and ducts, approved sealing, and ventilation and indoor air quality basics. Fabrication questions (outline area B, 9%) are table lookups in the SMACNA standards; the airflow math and the IAQ facts are concepts to know cold.
What the exam asks
- Airflow math: CFM from area and velocity, the friction rate for the Ductulator, and CFM per ton.
- Fan laws and static pressure: what changes with speed, and what total external static pressure measures.
- SMACNA fabrication lookups: pressure class, seal class, seams and joints, and approved sealing.
- NFPA 90A and NFPA 96 rules: fire and smoke dampers, grease duct material, clearances and cleanouts.
- Ventilation and indoor air quality: ERV versus HRV, filters, humidity and outdoor air rates.
Part 1 of 5
Sizing: how much air, how big a duct
Every duct job starts with how much air the system moves and how fast it can move through a given size. Learn these four ideas and the sizing questions turn into arithmetic.
Airflow scales with tonnage
Design cooling airflow runs about 350–400 CFM per ton. A 3-ton system at 400 CFM/ton needs roughly 1,200 CFM. In humid climates designers lean toward the 350 end — slower air over a colder coil removes more moisture.
Airflow = Tons × CFM per ton
Design supply airflow
3 tons × 400 CFM equals 1,200 CFM
Equal friction is the default sizing method
The equal friction method holds the friction rate — pressure drop per unit length, in inches of water column per 100 feet — constant for every duct run, and lets the duct size vary with the airflow each section carries. It's the standard approach for residential and light commercial design.
Friction rate = available static ÷ total effective length
The design friction rate is the available static pressure divided by the total effective length, scaled to 100 feet: (0.50 ÷ 250) × 100 = 0.20 in. w.c. per 100 ft. Total effective length is the measured duct plus the equivalent length of every fitting, on the supply side and the return side together. Leaving out the return or the fittings is the usual wrong answer.
Friction rate = (Available static ÷ Total effective length) × 100
Friction rate to take to the Ductulator
(0.50 in. w.c. ÷ 250 ft) × 100 equals 0.20 in. w.c. per 100 ft
Q = A × V, in both directions
Airflow in CFM is area in square feet times velocity in feet per minute. A 12 × 24 in. duct is 288 sq in., or 2 sq ft; at 800 FPM it carries 1,600 CFM. Turned around, velocity = CFM ÷ area. At a grille use the free area, not the face size. The trunk gets smaller after each takeoff because it only carries what is left: 1,000 − 240 − 360 = 400 CFM in the last section.
CFM = Area in sq ft × Velocity in FPM. Sq ft = sq in ÷ 144.
Area in square inches
24 in. × 12 in. equals 288 sq in.
Area in square feet
(24 in. × 12 in.) ÷ 144 equals 2.00 sq ft
Airflow
Area in sq ft × 800 FPM equals 1,600 CFM
Velocity = CFM ÷ Free area in sq ft. Free area = Face area × Free-area percent.
Free area
24 in. × 12 in. × 75%% ÷ 144 equals 1.50 sq ft
Velocity through the free area (the gross face area would understate it)
500 CFM ÷ free area equals 333 FPM
Airflow left in the trunk = Airflow leaving the air handler − Each branch takeoff
Airflow in the last trunk section
1,000 CFM − 240 CFM − 360 CFM equals 400 CFM
In your books: Sizing the duct is Manual D work. Take the friction rate to the Ductulator and read the duct size for each airflow.
Part 2 of 5
Fans, pressure and fittings
The blower has to push through everything outside the cabinet. Speed, fittings, flex and return paths decide whether the system moves the air it was sized for.
Fan laws and static pressure
Airflow changes directly with fan speed, static pressure with the square of the speed ratio, and horsepower with the cube. A 25% speed increase moves 25% more air and nearly doubles the motor load. Total pressure is static pressure plus velocity pressure. Total external static pressure is read across the blower and covers everything outside the cabinet: ducts, filter, grilles, and on a furnace the add-on coil.
CFM varies with the speed ratio. Static pressure varies with its square. Horsepower varies with its cube.
Speed ratio
1,000 RPM ÷ 800 RPM equals 1.25
New airflow
1,000 CFM × speed ratio equals 1,250 CFM
Static pressure multiplier
Speed ratio × speed ratio equals 1.56×
Horsepower multiplier
Speed ratio × speed ratio × speed ratio equals 1.95×
Fittings and flex make or break a run
A square-throat elbow has the largest loss; a long-radius elbow or turning vanes cut it sharply. A 45-degree or conical takeoff beats a straight collar punched into the trunk. Flex duct is rated fully extended: extra length, compression, sag and tight bends multiply its friction. Support flex about every 4 feet with wide hangers and keep sag to about 1/2 inch per foot. For the same area, round or near-square duct has the least friction.
Give the air a way back
A closed bedroom door with no return path pressurizes the bedroom and pulls the rest of the house negative. Transfer grilles, jumper ducts, door undercuts or dedicated returns fix it. Returns are sized for the same total airflow as the supply; an undersized return is noisy and cuts airflow. Return air is never taken from a garage, kitchen, bathroom, closet or furnace room.
Part 3 of 5
Building and sealing the duct
Fabrication questions are table lookups. The pressure class sets the gauge, reinforcement, joints and seal class, and the sealing material has to be one that holds up.
SMACNA runs on pressure class
Every table in the HVAC Duct Construction Standards is keyed to static pressure class (1/2, 1, 2, 3, 4, 6, 10 in. w.g.); 1 in. w.g. applies when the designer names none. Seal class follows: C at 2 in., B at 3 in., A at 4 in. and above — though the energy code wants every joint sealed anyway. Gauge trades against reinforcement spacing; the Pittsburgh lock is the standard longitudinal seam, S and drive the classic low-pressure transverse joint, TDC/TDF flanges the higher-pressure one.
Mastic, not duct tape
Duct joints get sealed with mastic or tapes listed and labeled for duct sealing (UL 181). Ordinary cloth-backed 'duct' tape is never the answer — its adhesive dries out and fails. Leaky ducts waste capacity and can pull humid unconditioned air into the system.
In your books: Duct construction and sealing detail is SMACNA territory. Fabrication questions name a width and a pressure class, so go straight to the SMACNA rectangular duct table for that class and read gauge, reinforcement and joint. Match the verb: build or seal means SMACNA, size means Manual D.
Part 4 of 5
Fire, smoke and grease
Ducts that cross rated walls or carry grease fall under NFPA rules. Most of these questions are numbers and device types you need to know cold.
Fire dampers and smoke dampers are different devices
A fire damper closes on heat: a fusible link, commonly 165°F, releases the blade at a rated wall or floor. A smoke damper is driven by a smoke detector or the fire alarm and is listed by leakage class. Combination dampers do both. Each one needs a service opening so the link or actuator can be inspected and reset. NFPA 90A covers buildings generally; NFPA 90B covers one- and two-family dwellings and spaces up to 25,000 cubic feet.
Grease duct is a different animal
NFPA 96: Type I hood over grease-producing appliances, Type II over heat and steam; duct 16 ga carbon steel or 18 ga stainless, continuously welded liquid-tight; cleanouts at each change of direction and every 12 ft on horizontals; filters at 45° or steeper; upblast fan 40 in. above the roof and 10 ft from intakes.
NFPA 96: clearance, slope, cleaning, suppression
An unenclosed grease duct keeps 18 inches from combustibles and 3 inches from limited-combustible material unless a listed wrap or enclosure reduces it. Horizontal runs slope back to the hood or a grease reservoir with no low spots. A Type I hood gets an automatic extinguishing system that also shuts off the fuel or power to the appliances. Inspection runs from monthly for solid-fuel cooking to annually for low-volume kitchens.
In your books: NFPA 96 questions are numbers: gauge, clearance, cleanout spacing and termination height. They sit in the duct and termination chapters. Tab them.
Part 5 of 5
Ventilation and indoor air quality
Fresh air, filters and humidity are the last piece. In Florida the humidity side is where systems get into trouble.
ERV = heat + moisture, HRV = heat only
A heat recovery ventilator exchanges only sensible heat between exhaust and incoming air; an energy recovery ventilator transfers moisture too. In Florida the ERV wins, because it sheds moisture from the incoming humid air and cuts the latent load.
Filters, humidity and CO2 are the IAQ trio
A higher MERV filter means a higher pressure drop — check blower capacity or add filter area. Target 30–60% RH (Florida's fight is the top end). Indoor CO2 above the outdoor level tracks ventilation per person; a CO alarm that follows the furnace means combustion products are getting into the house.
Exhaust always ends outdoors
Bath and kitchen exhaust discharges outside, never into an attic, crawl space or soffit cavity. The bathroom benchmark is 50 CFM intermittent or 20 CFM continuous. Dryer exhaust is 4-inch smooth metal, limited to 35 feet less the elbow deductions, with no screws projecting more than 1/8 inch inside, and it ends in a backdraft damper with no screen. A commercial kitchen hood needs makeup air roughly equal to the exhaust, interlocked to run with it.
Outdoor air: a people rate plus an area rate
The mechanical code's ventilation table gives two numbers for each occupancy: CFM per person and CFM per square foot. The zone needs the people rate times the occupants plus the area rate times the floor area. An office is 5 CFM per person plus 0.06 CFM per square foot. Homes follow the same idea with floor area plus bedrooms. Outdoor air intakes are set well away from exhausts, plumbing vents and other contaminant sources.
Outdoor air = People rate × Occupants + Area rate × Floor area
From people
5 CFM per person × 20 equals 100 CFM
From floor area
0.06 CFM per sq ft × 2,000 sq ft equals 120 CFM
Zone outdoor air
People part + area part equals 220 CFM
In your books: Ventilation rates are tables in the FBC Mechanical ventilation chapter. Tab it and read the number off the page rather than memorizing it.
Know these cold
The short list to have in your head on exam day. Every line is also a card in your flashcards.
- Equal friction method
- Same friction rate (pressure drop per 100 ft) for all runs; sizes vary with airflow
- Cooling airflow rule of thumb
- 350–400 CFM per ton (3 tons ≈ 1,200 CFM at 400)
- Approved duct sealing
- Mastic or UL 181-listed tape — never cloth-backed duct tape
- ERV vs HRV
- ERV transfers heat and moisture; HRV transfers heat only
- Condensate trap
- Keeps air handler suction from blocking the drain while letting water flow by gravity
- Default SMACNA pressure class
- 1 in. w.g. when the drawings do not designate one.
- Flame/smoke limit for duct materials
- Flame spread ≤25, smoke developed ≤50 (NFPA 90A).
- Fire damper rating
- 1½-hour in barriers under 3 hours; 3-hour in barriers rated 3 hours or more.
- Flexible air connector limit
- Not over 14 ft long; longer runs are flexible air duct or rigid duct.
- UL 181 listings
- 181A (A-P tape, A-M mastic, A-H heat-activated) for rigid fibrous glass duct; 181B (B-FX tape, B-M mastic) for flexible duct.
- HEPA
- 99.97% of 0.3-micron particles.
- Friction rate formula
- (Available static pressure ÷ total effective length) × 100 = in. w.c. per 100 ft.
- Total effective length
- Measured duct length + fitting equivalent lengths, supply and return sides together.
- Airflow formula
- CFM = area (sq ft) × velocity (FPM). Divide square inches by 144 to get square feet.
- Fan laws
- CFM varies with RPM; static pressure with RPM squared; horsepower with RPM cubed.
- Total pressure
- Static pressure + velocity pressure.
- Total external static pressure (TESP)
- Read across the blower, return side to supply side; compare it with the blower table to find the real airflow.
- Temperature split
- Return minus supply; roughly 18 to 22°F on a correctly charged system with proper airflow.
- Flex duct support
- About every 4 ft, sag no more than about 1/2 in. per foot of spacing, pulled fully extended.
- Metal duct hangers
- Not more than 10 ft apart under FBC-Mechanical 603.10, or per the SMACNA standard.
- Dryer exhaust
- 4-in. smooth metal, 35 ft maximum developed length less elbow deductions, backdraft damper, no screen.
- Bathroom exhaust
- 50 CFM intermittent or 20 CFM continuous, discharged outdoors.
- Fire damper vs smoke damper
- Fire: fusible link (commonly 165°F), UL 555. Smoke: detector or alarm actuated, UL 555S leakage class.
- NFPA 90B scope
- One- and two-family dwellings and spaces not over 25,000 cu ft. NFPA 90A covers other buildings.
- Grease duct clearance
- 18 in. to combustibles and 3 in. to limited-combustible material, unless a listed enclosure or wrap is used.
- NFPA 96 inspection schedule
- Monthly solid fuel; quarterly high volume; semiannually moderate volume; annually low volume.
- Fibrous glass duct limits
- About 2 in. w.g. and 2,400 FPM; never for grease, dryer or flue exhaust. Joints stapled about 2 in. on center and sealed with a UL 181A closure.
- Seal classes
- A = transverse joints, longitudinal seams and all wall penetrations; B = joints and seams; C = transverse joints only.
- Sheet metal gauge
- The numbers run backward: 18 gauge is thicker than 26 gauge.
- Ventilation rate (office example)
- 5 CFM per person + 0.06 CFM per sq ft of floor area.
- Throw
- Distance the air travels from an outlet before slowing to terminal velocity, commonly about 50 FPM.
- Furnace supply plenum clearance
- The listed clearance to combustibles applies to the plenum and the first 3 ft of supply duct.
Where it lives in your books
The real exam is open book. Knowing which book and which tab answer this topic is worth as much as memorizing it.
- HVAC References · 16 recommended tabsRACT is a 1,700-page textbook — it answers almost any fundamentals, electrical, or troubleshooting question, but only if you tab it by unit. Build the tab set below and trust the symptom tables over memory.
- Ductulator · 5 recommended tabsDuct sizing questions on the exam are Ductulator questions: given CFM and a friction rate (commonly 0.08 to 0.1 in. w.c. per 100 ft), read the round size, then the rectangular equivalent that fits the space. Practice the dial until you can read it in seconds — it is faster than any table.
- SMACNA Energy Systems · 6 recommended tabsEnergy questions are about which measure saves energy and why — economizers, setback, VFDs, high-efficiency equipment, duct sealing — and the simple-payback arithmetic that justifies them. Tab the measures chapter and the payback example.
- Florida Building Code · 18 recommended tabsCode questions give themselves away with words like 'minimum', 'required', or 'permitted'. Go to the code — never answer a code question from memory when the book is on the desk.
Reading isn't learning. Retrieval is.
107 questions in this domain, each with an explanation and source.